Case studyChemical ProcessingLegacy UpgradeControl Panels

VFD Retrofit for Plant Fans and Pumps

Across-the-line starters on a chemical plant’s boiler, feed water and dryer fans replaced with stainless VFD control panels, 50 to 150 HP — five installed and started up in the first round, six more built to match the next year.

50–150HP range
304 SSFree-standing enclosures
8 hrsStart-up per VFD, round one
11VFD panels, two rounds

The challenge

A chemical plant in Hamilton was running its boiler forced-draft fan, feed water pump and dryer combustion, booster and vapour fans on across-the-line starters — no speed control, full inrush on every start, and no way to trim airflow to the process. Every fan and pump ran flat out against a damper or a valve, and the plant was paying for the difference in energy.

The panels would live in a harsh environment, in direct sun, so enclosure climate control mattered as much as the drive inside. And the plant wanted a turn-key solution — design, panel build, installation and start-up from one company.

No speed controlFull inrush every startInefficient to run

The solution

Sheridan Automation designed and built free-standing 304 stainless VFD control panels: a main flanged disconnect with door interlock, enclosure heater and Vortex cooling on a thermostat, line and load reactors, and door-mounted E-stop, local start/stop, manual/local selector, speed potentiometer and drive keypad.

Round one — five panels — was supplied and field-installed, with Sheridan electricians running the power to each cabinet and the cabinet to each motor in teck cable and rigid conduit, then started up with eight hours of commissioning per drive. The following year, six more were built to mimic the first set, supplied for the plant to install.

Sheridan electricians on the installDrawings approved before buildTested & loaded before shippingBuilt to match, round two

Why a VFD saves energy

Across-the-line control runs the motor at full speed whenever it’s on. A VFD lets the motor match its speed to the actual process demand. On pumps and fans especially, even a small reduction in speed creates a very large reduction in energy consumption — power falls roughly with the cube of speed, so a fan running at 80% speed draws about half the power it drew at 100%.

Scope of work

Eleven panels, two rounds, one design.

Panel design & build

Free-standing 304 stainless enclosures with three-point latch and quarter-turn latches; complete electrical schematics and documentation, approved before build.

Enclosure climate control

Electric heater and Vortex cooling unit interconnected on a thermostat — sized for direct-sun siting and winter conditions alike, using readily available customer compressed air.

Door-mounted controls

Emergency stop, local start and stop, manual/local selector, speed potentiometer and drive keypad — 30 mm Type 4 devices.

Reactors & protection

Line and load reactors on every drive; main flanged disconnect with door interlock; new stainless non-fusible disconnects with viewing window on the 50 HP units.

Field installation, round one

Sheridan electricians ran power to each cabinet and cabinet to motor in teck cable or rigid conduit; existing motor wiring reused with fuse changes at the main disconnects.

Testing & start-up

Drives loaded with supplied parameters and tested before shipping; eight hours of start-up assistance per VFD, with the drive vendor’s technician on site.

On the floor

What it looks like.

VFD control panel in build with line and load reactors
In buildLine and load reactors and the drive stack on the back plate, in the shop. All connections carefully terminated with heat shrink and proper spacing.
Three Vortex enclosure coolers with solenoid valves on a stainless panel
Enclosure coolingVortex coolers and their solenoid valves, thermostat-controlled, mounted on the stainless enclosure — sized for year-round cooling on compressed air.
Labelled power terminals and ferruled control wiring at the drive
TerminationsLine, load and DC bus terminals labelled to the drawing; control wiring ferruled, tied and marked at both ends.
Finished stainless VFD control panel with the door open, in the shop before shipping
Finished panelDoor open before shipping — drive, fused disconnect and reactors inside; door-mounted devices and document pocket on the door.

Motors converted

Boiler FD fan — 150 HPFeed water pump — 100 HPDryer combustion air fan — 50 HPUnit booster fan — 50 HPDryer vapour fan — 50 HPSecond round: 3 × 50, 75, 100, 150 HP