VFD Retrofit for Plant Fans and Pumps
Across-the-line starters on a chemical plant’s boiler, feed water and dryer fans replaced with stainless VFD control panels, 50 to 150 HP — five installed and started up in the first round, six more built to match the next year.
The challenge
A chemical plant in Hamilton was running its boiler forced-draft fan, feed water pump and dryer combustion, booster and vapour fans on across-the-line starters — no speed control, full inrush on every start, and no way to trim airflow to the process. Every fan and pump ran flat out against a damper or a valve, and the plant was paying for the difference in energy.
The panels would live in a harsh environment, in direct sun, so enclosure climate control mattered as much as the drive inside. And the plant wanted a turn-key solution — design, panel build, installation and start-up from one company.
The solution
Sheridan Automation designed and built free-standing 304 stainless VFD control panels: a main flanged disconnect with door interlock, enclosure heater and Vortex cooling on a thermostat, line and load reactors, and door-mounted E-stop, local start/stop, manual/local selector, speed potentiometer and drive keypad.
Round one — five panels — was supplied and field-installed, with Sheridan electricians running the power to each cabinet and the cabinet to each motor in teck cable and rigid conduit, then started up with eight hours of commissioning per drive. The following year, six more were built to mimic the first set, supplied for the plant to install.
Why a VFD saves energy
Across-the-line control runs the motor at full speed whenever it’s on. A VFD lets the motor match its speed to the actual process demand. On pumps and fans especially, even a small reduction in speed creates a very large reduction in energy consumption — power falls roughly with the cube of speed, so a fan running at 80% speed draws about half the power it drew at 100%.
Scope of work
Eleven panels, two rounds, one design.
Panel design & build
Free-standing 304 stainless enclosures with three-point latch and quarter-turn latches; complete electrical schematics and documentation, approved before build.
Enclosure climate control
Electric heater and Vortex cooling unit interconnected on a thermostat — sized for direct-sun siting and winter conditions alike, using readily available customer compressed air.
Door-mounted controls
Emergency stop, local start and stop, manual/local selector, speed potentiometer and drive keypad — 30 mm Type 4 devices.
Reactors & protection
Line and load reactors on every drive; main flanged disconnect with door interlock; new stainless non-fusible disconnects with viewing window on the 50 HP units.
Field installation, round one
Sheridan electricians ran power to each cabinet and cabinet to motor in teck cable or rigid conduit; existing motor wiring reused with fuse changes at the main disconnects.
Testing & start-up
Drives loaded with supplied parameters and tested before shipping; eight hours of start-up assistance per VFD, with the drive vendor’s technician on site.
On the floor
What it looks like.
Motors converted
Capabilities used
Still starting big motors across the line?
Send us the motor list and the horsepower. You’ll be talking to the people who’ll build the panels.