A central-impression flexographic press moved from Manitoba to Ontario needed a safety system that would pass its Pre-Start Health and Safety Review — without taking away what the press was built to do. Sheridan designed it, built it, wired it and commissioned it, and handled the move.

10Locked guards — 8 decks, 2 bull-gear doors
6LEL gas detectors in the safety circuit
2Provinces — disconnected in one, reconnected in the other
1Safety PLC, programmed and commissioned

The challenge

A flexible packaging plant was relocating a central-impression flexographic press from Manitoba to Ontario. On arrival it fell under the Occupational Health & Safety Act and needed a new safety system to meet the Act and pass its Pre-Start Health and Safety Review before it could run.

Guarding a press this size is easy to get wrong. Lock the decks and the operators can’t jog; make the unwind area untouchable and nobody can splice. A safety circuit that fights the machine risks getting bypassed.

PHSR requiredLEL gas detectionFunction had to survive

The solution

Working with the safety engineers, Sheridan designed an electrical safety circuit around a SICK safety PLC that gives certifiably safe operation of the press without changing how it runs — every zone has a way in that the safety system controls, and a way to get running again that the operator controls.

The same crew disconnected the press at the old plant, reconnected it at the new one with the power distribution it needed and new QC lighting, installed every safety sensor, integrated the new controls with the press’s own PLC, drew the schematics, and commissioned the whole thing.

SICK safety PLCIntegrated with the press PLCTurn-key, including the move

How the safety system behaves

Every zone has a controlled way in, and a controlled way back to running.

The logic, zone by zone, as designed with the plant’s safety engineers and handed over in the PHSR package.

Rewind area — request to enter

Both doors solenoid-locked. The operator requests entry at a pendant; the press PLC confirms the outboard spindle is idle; the safety PLC drops the contactors on that spindle, the turret and the splice arm, disables the knife, then releases the lock and lights the pendant.

Rewind area — back to running

The lock re-engages if the door isn’t opened in time, or once the door is closed and reset is pressed. Both doors closed is signalled back to the press PLC. A door opened without a request is an E-stop.

Unwind area — area scanner

A tripped scanner drops the turret and splice-arm contactors and disables the knife; the press PLC is told so it can pause or cancel a splice in progress. Reset from a pendant at the main console, with a “reset required” light.

CI drum & print decks — standstill-locked

Eight deck guards and two bull-gear doors on safety-rated locks. The press PLC asks for guards to unlock; the safety PLC releases them only after a back-EMF standstill monitor confirms the drum has stopped.

Jog mode — without defeating the guards

Upside and downside guards lock independently, on the press PLC’s request, with lock status fed back. One side open leaves the drum jog-able; both sides open drops the drum contactors. Guards opened while running is an E-stop.

Inhibit start & back guards

An external-device-monitoring fault on any dual contactor holds the press off until it’s fixed. The unwind and rewind back guards are on dual-channel safety switches wired straight into the E-stop chain.

Scope of work

Sensors, safety PLC, contactors, schematics, commissioning — and the move.

  • SICK safety PLC, supplied, programmed and commissioned
  • HMI for safety-system monitoring and feedback
  • Schmersal safety-rated magnetic interlocks with feedback, all ten guards
  • SICK safety-rated door switches
  • Area scanners, unwind and rewind
  • Pushbutton reset stations and pilot lights throughout
  • Honeywell gas detection with six LEL detectors, in the safety circuit
  • Dual redundant safety contactors on every servo, with feedback
  • Complete electrical integration schematics
  • Electrical disconnection in Manitoba, reconnection in Ontario
  • Power distribution at the new location; new QC lighting

On the floor

What it looks like.

SICK safety PLC panel with safety relays, dual contactors and I/O modules
Safety PLC panelThe SICK safety PLC, dual contactors and I/O.
Sheridan technicians modifying the press control cabinets to add the safety PLC
Control Panel RetrofitRequired modifications of the control cabinet to add a safety PLC, contactors, control wiring and more.
Guard interlock switch fitted to a print-deck guard
Deck guard interlockA locked print-deck guard with its feedback switch.
LEL gas detector mounted on the press frame
Gas detectionAn LEL detector and the detection controller.

Got a machine that won’t pass its PHSR?